W-HL (high lift) Range

 WHL60 small

High Lift capacity Diesel fuel cleaning system.
Up to 70lit/min fuel polishing system, nominal flow rate 60lit/min, cleaning fuel to 2 micron absolute, removing both free and emulsified water, bacteria and particulate

 

 

 

 

 

 

  • • Advanced, high speed AC system, providing full control system and monitoring
    • Manual, Automatic (timer) and BMS control system
    • Unique easy-priming system
    • Integrated Fuel Flow Indicator
    • Recirculation or transfer action
    • 99.9 % free water removal in a single pass
    • 99 % emulsified water removal in a single pass
    • 2 micron final polish/fuel cleaning
    • Tank sizes up to 125,000 litres
  • Add-on options available

This email address is being protected from spambots. You need JavaScript enabled to view it.

Base Model (wall mounted)

W-HL060W-220

Max flow rate

70 lit/min (18.5 US gal/min)

Recommended tank size

Up to 125,000 litres (33,000 US gallons)

Finish options

IP55 Wall-mounted Frame Mounted, Enclosure

Particulate removal to

2 Micron

Control unit

Touch screen control

BMS** outputs

6

BMS** inputs

2

Power options

220v 50hz 1ph AC / 110v 690hz 1ph AC available

Fuse

3a 

Typical current

1a

Suction capability

6-7m max vertical lift, over 3m requires non-return valve fitted

Port sizes

1.5" BSP-P / NPT

Pump body

Steel

Pump type

Sliding Vane

Shaft

316 Stainless steel

Seal

Viton/FKM

Dimensions *

1000x1500x400mm (39x59x16in)

Weight *

85kg est. (187lbs)

CLEANING SPEED

Up to 70 lit/min - ideal for tank sizes up to 125,000 litres

POWER

220vAC

110vAc (option)

INSTALLATION

Wall Mounted, stair climbing trolley, weather-proof casing, towing unit, frame mounted

ADD-ONS

Absolute Polishing (to 0.5 micron), auto biocide dosing, WASP Connect (remote control of unit), particulate counter, Auto priming pumps, auto water drains, mobile & internet connectivity, drip tray, auto change-over for multiple fuel tanks, ModBus and FieldBus options.

Performance

1.5" hose, 0.5m lift, 77 lit/min

1.5" hose, 5m lift, 72 lit/min

1" hose, 3.5m lift, 62 lit/min

1" hose, 5m lift, 58 lit/min

Figures May 2020, tested with clean filter elements and 2-year-old diesel.

* Measurements are for the wall mounted version. Please enquire for measurements for others.

**BMS -Building Management System

 

w-pfs-installation-diagram

  • Ensure the system is securely fastened to a wall or other suitable solid structure.

  • The unit should have unique pipe work from any existing fuel driven equipment. The input to the WASP system should feed from the bottom of the fuel tank (via a ball valve and a foot valve or non return valve)

  • The system should pick-up fuel from the lowest point of the tank at one end, (below the level of the fuel feed to your engine) and ideally return it to the highest point at the opposite end.

  • The output should return to the tank at the top, opposite end to the input ideally.
  • The unit can be controlled via BMS, however it is capable of self operation and monitoring.
  • System must be primed before use and operation. It must also be primed after servicing; although with the aforementioned foot or non return valve installed, priming should only need to be done once after installation.
  • With power applied, please ensure the system’s time and date have been correctly set.
  • We recommend an internal pipe diameter of 3/4” for the 010 model and 1” for the others; however larger diameters will assist the unit as this reduces the frictional losses. Small diameters, long pipe runs or many bends in the pipe work will cause high frictional losses and cause the system to run slower than its maximum speed, or in extreme cases cause it to stop. Likewise high fuel lifts or fuel heads will also cause the unit to run slower.
  • In any typical fuel tank, the pipe feeding fuel to the engine is not at the bottom, however to successfully clean fuel, the pickup pipe going to the WB unit should be right at the bottom of the tank, below the engine feed.

 
 

 

Try our helpful new PRODUCT SELECTOR to select the model for your needs.

 

PDF Data Sheet for W-HL60 Quote Forms Add-on Options This email address is being protected from spambots. You need JavaScript enabled to view it. W-PFS-060 Gallery Product Selector Widget Case Studies PDF W-PFS PRODUCT RANGE 

Tags: Fuel Tank Size: 40,001 to 110,000 litresPower Options: 220v ACPower Options: 110v ACInstallation: Wall MountedInstallation: Frame Mounted
TOP